Tunnel foam spray fire extinguishing system

Key words:

Product category:

Product Details

Tunnel foam spray fire extinguishing system

The foam spray fire extinguishing system (for tunnels) divides the foam liquid and fire water supply provided by the balanced foam liquid supply device into two channels and sends them to the water control valve ( deluge valve, pressure reducing valve) , proportional mixer, balance valve, etc. A fire extinguishing system that uses a proportional mixer ( for tunnels) to mix to form a mixed liquid, and then sprays mist into the tunnel through a foam nozzle (non-aspiration type).

    The water supply pipeline and liquid supply pipeline of the foam spray fire extinguishing system ( for tunnels) in the servo state are filled with fire water and foam liquid, and the pressure is stabilized by a pressure stabilizing pump. When a fire breaks out in a tunnel and people cannot extinguish the fire or control the fire by self-rescue, the fire expands. After being detected by the fire detector, the fire alarm controller sends out a fire alarm signal and starts a delay to remind personnel to evacuate quickly. After the delay ends, The foam spray fire extinguishing system automatically enters the start-up procedure: after the fire signal detected by the fire detector is analyzed and processed by the fire alarm controller, the location of the fire is determined, and a start signal is sent to the proportional mixer closest to the fire center. Rain alarm When the valve is opened, the fire water and foam liquid flow to the proportional mixer at the same time, forming a foam mixture through the action of the proportional mixer, and the mixture is sprayed out in the form of mist from the foam nozzle to extinguish the fire. While sending a start signal to the proportional mixer , the fire alarm controller starts the fire pump and the balanced foam supply device to continuously supply fire water and foam liquid to the water supply pipeline and liquid supply pipeline respectively.

Main technical parameters of foam spray fire extinguishing system :

name

parameters

name

parameters

System design pressure

1.6MPa

Proportional mixer (tunnel foam spray control valve group) diameter

DN100

System working pressure range

0.6-1.2MPa

Proportional mixer (tunnel foam spray control valve group) flow rate

16~60(L/ s )

Foam mixture supply strength

6.5L · m2 /min

Rated working pressure of nozzle

0.35MPa

Mixing ratio of foam mixture

3%

Nozzle installation distance

5m

System fire extinguishing time

Increases with the increase in foam liquid storage capacity

PT6.6 type K=210 single nozzle protection area

Suitable for three-lane tunnels. When the installation height is 4.2~ 5m , the protection area is: 12.5×5 m2

Gear pump drive method

electric motor

PT4.4 type K=140 single nozzle protection area

Suitable for two-lane tunnels. When the installation height is 4.2~ 5m , the protection area is: 8×5 m2

Gear pump dry wear resistance time

Not less than 10 minutes

PT2.7 type K=86 single nozzle protection area

Suitable for single-lane tunnels. When the installation height is 4.2~5 m , the protection area is: 5×5 m2

 

Inquiry Now