Tunnel foam spray fire extinguishing system
Key words:
Product category:
Product Details
Tunnel foam spray fire extinguishing system
The foam spray fire extinguishing system (for tunnels) divides the foam liquid and fire water supply provided by the balanced foam liquid supply device into two channels and sends them to the water control valve ( deluge valve, pressure reducing valve) , proportional mixer, balance valve, etc. A fire extinguishing system that uses a proportional mixer ( for tunnels) to mix to form a mixed liquid, and then sprays mist into the tunnel through a foam nozzle (non-aspiration type).
The water supply pipeline and liquid supply pipeline of the foam spray fire extinguishing system ( for tunnels) in the servo state are filled with fire water and foam liquid, and the pressure is stabilized by a pressure stabilizing pump. When a fire breaks out in a tunnel and people cannot extinguish the fire or control the fire by self-rescue, the fire expands. After being detected by the fire detector, the fire alarm controller sends out a fire alarm signal and starts a delay to remind personnel to evacuate quickly. After the delay ends, The foam spray fire extinguishing system automatically enters the start-up procedure: after the fire signal detected by the fire detector is analyzed and processed by the fire alarm controller, the location of the fire is determined, and a start signal is sent to the proportional mixer closest to the fire center. Rain alarm When the valve is opened, the fire water and foam liquid flow to the proportional mixer at the same time, forming a foam mixture through the action of the proportional mixer, and the mixture is sprayed out in the form of mist from the foam nozzle to extinguish the fire. While sending a start signal to the proportional mixer , the fire alarm controller starts the fire pump and the balanced foam supply device to continuously supply fire water and foam liquid to the water supply pipeline and liquid supply pipeline respectively.
Main technical parameters of foam spray fire extinguishing system :
name |
parameters |
name |
parameters |
System design pressure |
1.6MPa |
Proportional mixer (tunnel foam spray control valve group) diameter |
DN100 |
System working pressure range |
0.6-1.2MPa |
Proportional mixer (tunnel foam spray control valve group) flow rate |
16~60(L/ s ) |
Foam mixture supply strength |
6.5L · m2 /min |
Rated working pressure of nozzle |
0.35MPa |
Mixing ratio of foam mixture |
3% |
Nozzle installation distance |
5m |
System fire extinguishing time |
Increases with the increase in foam liquid storage capacity |
PT6.6 type K=210 single nozzle protection area |
Suitable for three-lane tunnels. When the installation height is 4.2~ 5m , the protection area is: 12.5×5 m2 |
Gear pump drive method |
electric motor |
PT4.4 type K=140 single nozzle protection area |
Suitable for two-lane tunnels. When the installation height is 4.2~ 5m , the protection area is: 8×5 m2 |
Gear pump dry wear resistance time |
Not less than 10 minutes |
PT2.7 type K=86 single nozzle protection area |
Suitable for single-lane tunnels. When the installation height is 4.2~5 m , the protection area is: 5×5 m2 |