The special foam spray nozzle for tunnels is a non-aspiration type, a combined nozzle composed of two or more independent nozzles. According to the size of the protected area, the foam nozzles are divided into three lanes, two lanes and single lane nozzles.
Tunnel special foam spray nozzle parameter table
name |
parameters |
name |
parameters |
System design pressure |
1.6MPa |
Nozzle installation position |
Upper part of tunnel side wall |
Fixed work stress |
0.35MPa |
Nozzle installation distance |
5m |
Working pressure range |
0.35~1.2MPa |
PT6.6 type K=210 single nozzle protection area |
Suitable for three-lane tunnels. When the installation height is 4.2~ 5m , the protection area is: 12.5×5 m2 |
Entrance diameter |
DN40 |
PT4.4 type K=140 single nozzle protection area |
Suitable for two-lane tunnels. When the installation height is 4.2~ 5m , the protection area is: 8×5 m2 |
Material |
copper alloy |
PT2.7 type K=86 single nozzle protection area |
Suitable for single-lane tunnels. When the installation height is 4.2~5 m , the protection area is: 5×5 m2 |
Connection thread |
Rc1 1 /2 |
|
|