Special foam spray nozzle for tunnels

Key words:

Product category:

Product Details

Special foam spray nozzle for tunnels

The special foam spray nozzle for tunnels is a non-aspiration type, a combined nozzle composed of two or more independent nozzles. According to the size of the protected area, the foam nozzles are divided into three lanes, two lanes and single lane nozzles.

Tunnel special foam spray nozzle parameter table

name

parameters

name

parameters

System design pressure

1.6MPa

Nozzle installation position

Upper part of tunnel side wall

Fixed work stress

0.35MPa

Nozzle installation distance

5m

Working pressure range

0.35~1.2MPa

PT6.6 type K=210 single nozzle protection area

Suitable for three-lane tunnels. When the installation height is 4.2~ 5m , the protection area is: 12.5×5 m2

Entrance diameter

DN40

PT4.4 type K=140 single nozzle protection area

Suitable for two-lane tunnels. When the installation height is 4.2~ 5m , the protection area is: 8×5 m2

Material

copper alloy

PT2.7 type K=86 single nozzle protection area

Suitable for single-lane tunnels. When the installation height is 4.2~5 m , the protection area is: 5×5 m2

Connection thread

Rc1 1 /2

 

 

 

Inquiry Now