Dry powder fire extinguishing equipment ZFP1000A

Key words:

Fire extinguishing dry powder

Product Details

(1)Equipment composition of dry powder fire extinguishing system

The ZFP type dry powder fire extinguishing system equipment mainly consists of dry powder tanks, driving cylinder groups, starting cylinder groups, one-way valves, collecting pipes, pressure reducers, pneumatic three-way ball valves, safety valves, starting valves, release ball valves, selection valves, dry powder nozzles, and other components.

(2)Main performance parameters of dry powder fire extinguishing system

 

Serial Number Project

Technical parameters

1

model

ZFP250A

ZFP500A

ZFP1000A

2

Type of filling dry powder ABC type dry powder ABC type dry powder ABC type dry powder

3

Dry powder filling capacity

250 kg

500 kg

1000 kg

4

Number of driving cylinder groups

2

3

6

5

Driving cylinder filling pressure(MPa)

13.5

6

Maximum working pressure(MPa)

1.6

7

Minimum working pressure(MPa)

0.5

8

Inflation time

≤20 s

9

Effective discharge time

Total flooding:≤30 s

Indoor parts:≥30 s

Places with a risk of re ignition outdoors or indoors:≥ 60 s

10

Dry powder residue rate

5%

2% 3%

11

Fully submerged protected space(m3

365

754

1492

12

Ambient temperature

-20℃~+50℃

(3)Operation mode of dry powder fire extinguishing system

The driving cylinder group of this system includes three starting methods, namely automatic start, manual start, and mechanical emergency start.

      Start automatically:

When a fire occurs in the protective zone, the smoke and temperature detectors inside the protective zone detect smoke and temperature signals, transmit them to the fire alarm controller, and the controller emits an audible and visual alarm. At the same time, the controller outputs a signal to drive the solenoid valve to open the gas cylinder, activate the high-pressure gas in the gas cylinder, and activate the gas cylinder group through the gas control pipe; The power gas released by the driving cylinder group is collected by the high-pressure hose into the manifold, and the high-pressure gas entering the gas transmission pipeline is depressurized by a pressure reducer (set at 1.4~1.6 MPa before leaving the factory, and the outlet pressure of the pressure reducer is adjustable) before entering the dry powder storage tank, and the system begins to pressurize. When the pressure (displayed on the pressure gauge on the dry powder storage tank) reaches 1.3~1.4MPa, open the start valve on the dry powder storage device and open the dry powder release valve. The dry powder enters the spraying pipeline and nozzle through the release valve.

     Manual Start:

When a fire occurs in the protective zone, the external detector of the firefighter system receives a fire alarm signal or presses the controller start button according to actual needs, and the dry powder system starts working.

     Emergency Operations:

In an emergency, immediately pull out the manual safety pin of the electromagnetic drive device on the starting cylinder container valve, press the manual pressure cap, open the container valve, and start the cylinder to open the other driving cylinder groups, release valves, and selection valves in order to start the system.

Attention: Mechanical emergency startup is not a part of the normal system startup and can only be used as a final measure in emergency situations!